Resources › Data Centres
Keeping Standby Diesel Ready: Fuel Quality, Testing and Monitoring for Data Centres
Most of the diesel at a data centre is never burned in an emergency. It waits, and waiting is what makes it go wrong.
- Fuel Quality
- Testing
- Filtration
- Monitoring
Diesel stored for standby generators can sit for months between test runs, and over that time water, microbial growth, oxidation and sediment can degrade it. Data centres keep it ready with a routine rather than a single check. Sample and test the fuel on a regular schedule agreed with the fuel supplier and generator manufacturer. Drain water from tank low points, and use filtration with water separation on the transfer system, with recirculation through filters on bulk tanks where fuel sits for long periods. Fit filtered breathers to keep moisture out, monitor levels and alarms remotely, and clean tanks when testing shows a problem. Keep records of every test, delivery and service, so fuel condition can be shown to auditors and insurers.
A data centre's diesel reserve is designed to be used rarely. Generators are run for tests, and the fuel they burn is topped up, but the bulk of the reserve can sit in the tank for a long time. When an outage comes, that fuel has to be as clean as the day it was delivered.
This guide sets out a practical routine for keeping standby diesel in condition at a data centre, as part of A-FLO's data centre fuel and power solutions. The causes of fuel degradation are covered in more depth in A-FLO's articles on how long you can store diesel, diesel bug and water in diesel.
96 Tank level readings a day possible with FLUIDBOT remote monitoring
10 micron Water-separating filtration available on GENCUBE generator tanks
4 Main threats to stored diesel: water, microbes, oxidation and sediment
What Happens to Diesel That Waits
- Water. Condensation forms as a tank breathes through daily temperature changes, and water settles at the bottom.
- Microbial growth. Bacteria and fungi live where fuel meets water, forming sludge that blocks filters.
- Oxidation. Over time, fuel reacts with air and forms gums and sediment.
- Sediment. Rust, dust and the products of degradation settle and are picked up when the generator starts drawing.
A generator that has run perfectly in a 30 minute test can block its filters during a long outage, because a long run draws fuel from deeper in the tank than a short test ever does.
A Fuel Quality Routine for Data Centres
Test on a schedule
Take samples from the bottom and middle of each bulk tank and send them for testing on a schedule agreed with the fuel supplier and generator manufacturer. Test new deliveries too, before or as they are received.
Drain water
Check tank low points and filter bowls for water and drain it as part of routine maintenance.
Filter on transfer
Filter fuel with water separation as it moves from bulk storage to the day tanks, so the generators receive clean fuel.
Recirculate long-stored fuel
Where fuel sits for long periods, recirculating it through filters, often called fuel polishing, removes water and particles before they build up.
Keep moisture out
Fit filtered breathers, keep fill points and inspection hatches sealed, and fix leaks that let water in.
Clean when testing says so
Where testing shows sludge, microbial growth or heavy sediment, clean the tank. A-FLO's guide to diesel tank cleaning and maintenance covers what is involved.
Turnover helps
Fuel that is used and replaced has less time to degrade. Generator test runs consume some of the reserve, and refilling with fresh fuel keeps the stock turning over. Plan test runs and deliveries with that in mind.
Monitoring the Reserve
Knowing the fuel is clean is half the job. Knowing how much there is, and being told when something changes, is the other half.
Levels
Automatic tank gauging
LEVELTRACK and FLUIDLEV gauges measure tank levels continuously and report them remotely.
Alerts
Remote monitoring
FLUIDBOT gives up to 96 level readings a day with SMS and email alerts on customisable thresholds, over cellular or satellite connectivity.
Integration
Facility systems
Tank gauges, pumps and alarms can interface with the facility's monitoring systems, so fuel status sits with the rest of the plant.
A level that falls with no generator running is a leak or an unrecorded draw. A level that rises with no delivery can mean water. Both show up early with continuous monitoring.
Records and Servicing
- Keep a fuel log. Deliveries, test runs, sample results, water drained and filter changes, in one place.
- Keep certificates. Delivery dockets and test reports show the fuel's history.
- Schedule servicing. Filters, breathers, pumps, gauges and alarms on a fixed service plan.
- Review after every outage. Check fuel quality and filters after the generators have run for a long period.
A-FLO's service and maintenance team offers inspection, tank maintenance, filtration, fuel testing and servicing for fuel storage infrastructure. For the fuel transfer side of the system, see bulk tanks and day tanks for data centre generators.
What Goes Wrong
- Testing only the generators. Engines are run monthly, but the fuel is never sampled.
- Sampling only the top of the tank. Water and sludge sit at the bottom.
- No water drain routine. Water builds up until it reaches the outlet.
- Breathers without filters. Every temperature swing draws in moist air.
- No record of fuel age. Nobody can say how old the fuel in the tank is.
- Short test runs only. A 30 minute run never draws on the fuel a long outage will.
Frequently Asked Questions
How do data centres keep stored diesel usable?
With a routine: regular fuel sampling and testing, draining water, filtering fuel with water separation as it is transferred, recirculating long-stored fuel through filters, keeping moisture out, monitoring levels remotely and cleaning tanks when testing shows a problem.
How often should standby generator diesel be tested?
On a schedule agreed with the fuel supplier and generator manufacturer, and when new deliveries arrive. Sample from the bottom and middle of each bulk tank, not just the top.
What is fuel polishing?
Recirculating stored diesel through filters and water separators to remove water and particles while it sits in the tank, so it stays closer to its delivered condition.
Why do generators fail on long runs when they pass short tests?
A long run draws far more fuel from deeper in the tank, where water, sludge and sediment collect. That can block filters that a short test run never troubles.
How can a data centre monitor its diesel reserves?
Automatic tank gauging and remote monitoring report tank levels continuously, with configurable alerts. A-FLO offers LEVELTRACK, FLUIDLEV and FLUIDBOT, which can send SMS and email alerts and interface with facility systems.
Does A-FLO provide fuel testing and servicing for data centres?
Yes. A-FLO offers inspection, tank maintenance, filtration, fuel testing and related servicing for diesel storage, fuel transfer equipment and tank monitoring systems.
What records should a data centre keep for its fuel?
Deliveries and their dockets, fuel test reports, generator test runs, water drained, filter changes and service visits, kept together so the fuel's condition and history can be shown.